6-12SectionProgramming Console Function
223
6-12-2 Connection Method
The connection method is exactly the same as for the NT Link (1:1). Refer to
Section 4 Connecting to the Host from the RS-232C Port or Section 5 Connect-
ing to the Host from the RS-422A/485 Port for details on connecting to the PC.
* When using the Programming Console function with a CQM1H, turn ON pin 7 of
the DIP switch on the front of the CQM1H’s CPU Unit.
The connection method is the same as for the NT Link (1:1). With a CPM1, con-
nect the RS-232C cable to the peripheral port via a CPM1-CIF01 RS-232C
Adapter or CPM1-CIF11 RS-422A Adapter.
Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5
Connecting to the Host from the RS-422A/485 Port for details on connecting to
the PC.
The connection method is the same as for the NT Link (1:1). Connect to the PC’s
communications connector with a CPM2C-CN111 or CS1W-CN114/118 Con-
necting Cable, a CPM1-CIF01 RS-232C Adapter, or a CPM1-CIF11 RS-422A
Adapter.
Refer to Section 4 Connecting to the Host from the RS-232C Port or Section 5
Connecting to the Host from the RS-422A/485 Port for details on connecting to
the PC.
* When using the Programming Console function with a CPM2C, turn ON pin 2 of
the DIP switch on the front of the CPM2C’s CPU Unit.
The connection method is exactly the same as for the NT Link (1:N) (standard or
high-speed). Refer to Section 4 Connecting to the Host from the RS-232C Port
or Section 5 Connecting to the Host from the RS-422A/485 Port for details on
connecting to the PC. The standard or high-speed 1:N NT Link can be used.
The Programming Console function can be used only when the PT’s unit num-
ber is set to 0. Only one unit using the Programming Console function can be
connected to each of the PC’s ports (built-in RS-232C port and peripheral port).
With the CS1G/CS1H, the Programming Console function can be used simulta-
neously at both the built-in RS-232C port and peripheral port. Furthermore, the
Programming Console function can be started at the RS-232C port while a Pro-
gramming Console is connected to the peripheral port.
CQM1, CQM1H,
C200HX/HG/HE(-ZE), or
SRM1
CPM1 or CPM2A
CPM2C
CS1G/CS1H