Schneider Electric LUFP7 Switch User Manual


 
86
6. Configuring the Gateway
6.13. Adding a Broadcaster Node
A broadcaster node does not correspond to any Modbus slave in particular, as it applies to all Modbus slaves.
All the commands which will be configured for this node will be transmitted with the “Slave Address” field set to
16#00. This means that all of the slaves will run the command, but that none of them will respond to it.
To add a broadcaster node, select “Sub-Network”, then choose “Add
Broadcaster” from the “S
ub-Network” menu. The broadcaster node created in
this way does not count in the limit on the number of configurable nodes. A
simple example is shown opposite:
The addition and configuration of a Modbus command in the list of broadcaster
node commands is done in the same way as for other nodes, but with the
following differences:
- The list of standard Modbus commands which can be used in broadcast is
considerably smaller. Only functions 16#06 and 16#10 can be used (see list
in chapter 6.11.2, page 70).
- The command is made up of a query, but does not include any response. The query bears the name of the
command itself, instead of the name “Query.” Also, each broadcast command only consumes one of the
50 queries and responses allowed by the gateway, as there is no possible response for such a command.
- The value of the query’s “Minimum time between broadcasts (10ms)” field must be changed if the default
value (1 second) is not suitable.
- The value of the query frame’s “Slave Address” field is set to 16#00.
Please see chapter 6.11.2.2 Configuring the Query, page 72, for further details on how to configure a Modbus
query.