2-32 Sun Netra CP3220 Blade Server User’s Guide • January 2010
2.3.10.2 Changing the OOS LED Color
The color of the Out-of-service (OOS) LED can be set to red or amber by moving
jumper 2 to the appropriate position. Amber is the default color for the OOS LED.
To change the Jumper 2 position to red:
1. Remove the jumper housing from the default (amber) position (P2/P3) and
move it to the red position (P1/P2).
FIGURE 2-12 Jumper 2 in the Red Position
2. Reinstall the blade server.
Use the procedure in Section 2.2.3.2, “Installing the Blade Server Into the Shelf”
on page 2-12.
2.3.11 Changing OOS LED Behavior
When blade servers are shipped from manufacturing, they are set to the default LED
behavior. The default OOS LED behavior is as follows:
■ IPMC lights up OOS LED if it detects POST failure.
■ IPMC lights up OOS LED if it fails to power up the blade server.
■ Most of the time, OOS LED remains OFF.