Appendix A Physical and Environmental Specifications 117
Environmental Compliance Information
■ Electromagnetic compatibility
■ Immunity: The server conforms to EN55024.
■ Emissions: The server conforms to EN55022 Class A and FCC Class A.
■ Safety
The system conforms to UL 1950 (3rd edition), EN60950
Operating Power Statistics
* The in-rush current decays to the normal operating current in less than 200 msecs.
Caution – The power supply continues to regulate all outputs for at least 17 ms
after AC power is removed.
Note – Logic ground and chassis ground are connected internally.
TABLE A-2 Operating Power Statistics
Maximum operating current 1.3A @ 100 VAC
Typical operating current See “Calculating Power Consumption” on
page 118
Maximum in-rush
current (cold start)*
40A peak at 115V
25˚C
Maximum in-rush
current (warm start, or upon a restart 20 to
200 msecs after power has been removed
*
)
100A peak at 115V
25˚C
Operating input voltage range 90 to 264 Vrms
Voltage frequency range 47 to 63 Hz
Power factor 0.9 to 0.99
Maximum volt-ampere rating 130 VA
BTU/hr 500 MHz processor: 148 (min), 280 (max).