Xantrex Technology XDC 20-600 Power Supply User Manual


 
Remote Operation
4–6 TM-XDOP-01XN
Pin Connections
Table 4-1
User Line Pins
Pin # Function Input/Output
A1 Aux Status Line A Output
A2 Aux Status Line B Output
A3 External Trigger 4–12V Input
A4 Safety Interlock (Shutdown) 4–12V Input
A5 Safety Interlock (Shutdown) GND Input
A6 User Power, 5–12Vdc Input
A7 User Ground Input
Figure 4-2
Schematic For User Line Interface
Vf = 1.3V TYP, 1.5V MAX
If = 10mA Recommended, 90mA MAX
CNY17-2
CNY17-2
508 Ohm
0.4W
508 Ohm
0.4W
CNY17-2
CHASSIS POTENTIAL ISOLATED USER LINES
CNY17-2
USER LINES
TM-XDOP-01XN.book Page 6 Monday, July 17, 2006 11:19 AM