Xantrex Technology XDC 20-600 Power Supply User Manual


 
Specifications and Characteristics
A–4 TM-XDOP-01XN
Table A-3
Specifications for 12000 Watt units (10V to 60V Models)
Models 10-1200 20-600 30-400 40-300 60-200
Output Ratings:
Output Voltage
a
Output Current
b
Output Power
a. Minimum output voltage is <0.3% of rated voltage at zero output setting.
b. Minimum output current is <0.2% of rated current at zero output setting when measured with rated load resistance.
0–10 V
0–1200 A
12000 W
0–20 V
0–600 A
12000 W
0–30 V
0–400 A
12000 W
0–40 V
0–300 A
12000 W
0–60 V
0–200 A
12000 W
Line Regulation:
c
Voltage (0.01% of Vmax)
Current (0.1% of Imax)
c. For input voltage variation over the AC input voltage range, with constant rated load.
1mV
1200 mA
2mV
600 mA
3mV
400 mA
4mV
300 mA
6mV
200 mA
Load Regulation:
d
Voltage (0.05% of Vmax + 5 mV)
Current (0.2% of Imax + 40 mA)
d. For 0–100% load variation, with constant nominal line voltage.
10 mV
2440 mA
15 mV
1240 mA
20 mV
840 mA
25 mV
640 mA
35 mV
440 mA
Meter Accuracy:
Voltage (0.15% of Vmax)
Current (0.5% of Imax)
15 mV
6A
30 mV
3A
45 mV
2.0 A
60 mV
1.5 A
90 mV
1A
Output Noise (0–20 MHz):
Voltage (p–p) 75 mV 75 mV 75 mV 75 mV 100 mV
Output Ripple (rms):
Voltage
Current
e
e. Current mode noise is measured from 10% to 100% of rated output voltage, full current, unit in CC mode.
10 mV
6200 mA
10 mV
3200 mA
12 mV
2000 mA
15 mV
1500 mA
15 mV
900 mA
OVP Adjustment Range:
(0% to 103% of Vmax) 0–10.3 V 0–20.6 V 0–30.9 V 0–41.2 V 0–61.8 V
Efficiency:
f
f. Typical efficiency at nominal input voltage and full output power.
0.85 0.87 0.87 0.87 0.89
Drift (30 minutes):
g
Voltage (0.04% of Vmax)
Current (0.6% of Imax)
g. Maximum drift over 30 minutes with constant line, load, and temperature, after power on.
4mV
7200 mA
8mV
3600 mA
12 mV
2400 mA
16 mV
1800 mA
24 mV
1200 mA
Drift (8 hours):
h
Voltage (0.02% of Vmax)
Current (0.05% of Imax)
h. Maximum drift over 8 hours with constant line, load, and temperature, after 30 minute warm-up.
2mV
600 mA
4mV
300 mA
6mV
200 mA
8mV
150 mA
12 mV
100 mA
Temperature Coefficient:
i
Voltage (0.04% of Vmax/°C)
Current (0.06% of Imax/°C)
i. Change in output per °C change in ambient temperature, with constant line and load.
4mV
720 mA
8mV
360 mA
12 mV
240 mA
16 mV
180 mA
24 mV
120 mA