PN9108 User Manual
32
Outlet Groups:
The bottom Configuration panel (refer back to page 29) lets you select the
outlets that you want to put together as an outlet group. Outlet groups enable
control actions to be carried out on the entire group at the same time, rather than
repeatedly performing the same action on each individual outlet. You can have
four outlet groups per station, and each group can be given a distinctive name.
The maximum number of characters for the name is 15.
UPS:
The PN9108 provides simple signal UPS support. If you connect a UPS to
the PN9108's RS-232 port, and enable the UPS function, should the main
power be interrupted and the UPS kick in, the PN9108 can initiate a safe
shutdown for all of the computers that have been cabled and configured
for a safe shutdown.
To enable the UPS function:
Put a check in the Enable UPS checkbox
Configure the pin assignments and polarities according to the
documentation for your UPS.
Set the power outlet configuration for each of the affected ports to one
of the safe shutdown options (seeModem Ring Resume* and System
after AC Back* in the table on page 30).
PN9108
UPS