HP (Hewlett-Packard) MSL6000 series Computer Drive User Manual


 
MSL6000 series tape library user guide 119
307A Diag get drive 2 status failed
(Failed to get drive status, communication
error.)
Press the Enter button to reboot.
Ensure the drive shows good status
through the drive status window.
Deactivate the drive using the GUI control
panel maintenance menu.
Reseat drive.
Check cabling.
Load/unload a cartridge to the drive to
verify.
Check the tape cartridge used in the last
operation for damage.
Run the cartridge cycle diagnostic to
verify.
307B Diag get drive 3 status failed
(Failed to get drive status, communication
error.)
Press the Enter button to reboot.
Ensure the drive shows good status
through the drive status window.
Deactivate the drive using the GUI control
panel maintenance menu.
Reseat drive.
Check cabling.
Load/unload a cartridge to the drive to
verify.
Check the tape cartridge used in the last
operation for damage.
Run the cartridge cycle diagnostic to
verify.
3082 Drive Stow Failed, Media Returned to
Source
Press the Enter button to clear the
message.
Use only media approved for the drive
type.
Invalid user initiated operation. Set
parameters correctly and try again.
3083 Drive Stow Failed, Media Remains in
Drive
Press the Enter button to clear the
message.
Invalid user initiated operation. Set
parameters correctly and try again.
Ensure cartridges are in magazines.
Table 10 Fault Symptom Codes (continued)
FSC Message ERP