Liebert POWER PROTECTION STATIC TRANSFER SWITCH Switch User Manual


 
Event Message Help Text
116
16.0 EVENT MESSAGE HELP TEXT
Key:
ALL CAPS = event message displayed in the Event Display panel in the lower left corner of the LCD display.
Indented text = help text shown in the Display Panel in the lower right corner of LCD display.
BOLD = commands that are sent through the RS-232 port.
S1 SCR SHORT
Source 1 SCR Short.
One or more of the SCRs for Source 1 has shorted. Transferring between sources has been inhibited.
Contact Liebert for technical support at 1-800-LIEBERT (800-543-2378).
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2 system
from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not already full.
This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
S2 SCR SHORT
Source 2 SCR Short.
One or more of the SCRs for Source 2 has shorted. Transferring between sources has been inhibited.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2 system
from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not already full.
This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
S1 SCR OPEN
Source 1 SCR Open.
One or more SCRs on Source 1 is open. Transferring between sources has been inhibited.
Contact Liebert for technical support at 1-800-LIEBERT (800-543-2378).
STS2 output has been transferred to Source 2.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the STS2 system
from a terminal, type SH and press RETURN on your keyboard to turn off the audible alarm.
This event and the system status surrounding it have been written to a History Log if the History Logs were not already full.
This event was also written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.