Liebert POWER PROTECTION STATIC TRANSFER SWITCH Switch User Manual


 
Installation Drawings
21
Figure 9 Outline drawing: 400 – 600 amp STS2 with a key lockout switch option
FRONT VIEW SIDE VIEW
CONTROL CABLE
TOP ENTRY AREA
CABLE
TOP ENTRY AREA
EXHAUST
CONTROL CABLE
BOTTOM ENTRY AREA
POWER CABLE
BOTTOM ENTRY
BOTTOM VIEW TOP VIEW
GRAVITY
FRONT
FRONT
MAX. DOOR SWING 180° (TYP)
CENTER
GRAVITY
CENTER
SEE DETAIL A
AREA
CENTERS
12MM
CASTER
CENTERS
AIR
12MM CENTERS
CASTER
CENTERS
DO NOT
BLOCK
AIR INTAKE AREA
AIR
FILTER
POWER
OUTLINE DRAWING
400 - 600 AMP WITH KEY LOCKOUT SWITCH OPTION
STATIC TRANSFER SWITCH 2
KEY LOCKOUT
SWITCH
NOTES:
1. ALL DIMENSIONS ARE IN INCHES AND (MILLIMETERS).
2. 18" (457MM) MIN. CLEARANCE ABOVE UNIT REQUIRED FOR AIR EXHAUST.
3. INSTALLATION AND SERVICE ACCESS REQUIRED IN FRONT ONLY.
4. HEAT OUTPUT: 6970 BTU/HR (2.04 KW/HR) MAX. FOR 400A SWITCH.
10520 BTU/HR (3.08 KW/HR) MAX. FOR 600A SWITCH.
5. WEIGHT - 1200 LBS. (544 KG)
6. UNIT BOTTOM IS STRUCTURALLY ADEQUATE FOR FORKLIFT HANDLING.
7. KEEP CABINET WITHIN 15 DEG. OF VERTICAL WHILE HANDLING.
8. COLOR - IBM OFF WHITE.
9. OPEN DOOR TO REPLACE AIR FILTER, DISPOSABLE TYPE, SIZE 1X25X25.
10. THREADED MOUNTING HOLES (SEE DETAIL A) ARE PROVIDED FOR SEISMIC
ANCHORING OR FLOOR STAND. MOUNTING BOLTS MUST BE THREADED INTO
THE UNIT MOUNTING HOLES FROM UNDERNEATH THE UNIT BASE. IF FLOOR
STAND IS USED, THE CASTERS MUST REST ON THE FLOOR STAND TO
SUPPORT THE WEIGHT OF THE UNIT.
FRONT OF UNIT SHOWN
WITHOUT SIDE PANEL
DETAIL A
MOUNTING
HOLE (4) TYP
(SEE NOTES
10)
12MM DIA
THREADED
LEVELER
(965)
38.0
(923)
36.3
(474)
18.6
(794)
31.3
(292)
11.5
(116)
4.6
(343)
13.5
(544)
21.4
(267)
10.5
(337)
13.3
(435)
17.1
(88) 3.5
(548)
21.6
(736)
29.0
(25)
.97 REF
(825)
32.5
(910)
35.8
(399)
15.7
(130)
5.1
(326)
12.8
(198)
7.8
(752)
29.6
(228)
9.0
(69.8)
2.75 (TYP)
PS211401 REV. NO. 1
(815)
32.1
(1956)
77.0
(372)
14.6