Liebert POWER PROTECTION STATIC TRANSFER SWITCH Switch User Manual


 
Communication Interfaces
80
Group 3:
User
Settings
1
SRC1 Fast Undervoltage
Setpoint
Integer In % of nominal below nominal
2
SRC1 Slow Undervoltage
Setpoint
Integer In % of nominal below nominal
3
SRC1 Slow Undervoltage
Detect Delay
Integer In number of lines cycles
4
SRC1 Overvoltage
Setpoint
Integer In % of nominal above nominal
5
SRC1 Overvoltage Detect
Delay
Integer In 1/4 lines cycles
6
SRC1 I peak Transfer
Setpoint
Integer x 10
7
SRC2 Fast Undervoltage
Setpoint
Integer In % of nominal below nominal
8
SRC2 Slow Undervoltage
Setpoint
Integer In % of nominal below nominal
9
SRC2 Slow Undervoltage
Detect Delay
Integer In number of lines cycles
10
SRC2 Overvoltage
Setpoint
Integer In % of nominal above nominal
11
SRC2 Overvoltage Detect
Delay
Integer In 1/4 lines cycles
12
SRC2 I peak Transfer
Setpoint
Integer x 10
13
Max. Transfer Phase
Angle
Integer In degrees
14
Output Frequency
Deviation
Integer Freq. in Hz x 10
1 5 R e T r a n s f e r D e l a y T i m e I n t e g e r I n s e c o n d s
16 Horn Volume Integer Range: 1-10
17 Critical Option Enabling Bitpacked See section 12.1.3.
18
Non-Critical Option
Enabling
Bitpacked See section 12.1.3.
Group 4:
Event Mask
Settings
1 to
63
Event Mask settings for
faults
Event Mask See section 12.1.4.
64 to
143
Event Mask settings for
alarms
Event Mask See section 12.1.4.
Table 12 Group settings and values (continued)
Group Item: Description Value Type Value Notes