National Instruments NI CVS-1450 Series Switch User Manual


 
Chapter 3 LEDs, DIP Switches, and Connectors
© National Instruments Corporation 3-5 NI CVS-1450 Series User Manual
IP RESET Switch
To clear the CVS-1450 device IP settings, move the IP RESET switch to
the ON position and reset the CVS-1450 device. Use IP RESET to reset
the TCP/IP settings when moving the system from one subnet to another or
when the current TCP/IP settings are invalid.
Resetting the CVS-1450 device with the IP RESET switch in the ON
position resets the IP address to 0.0.0.0. You can then set up a new network
configuration for the CVS-1450 device from a development machine on the
same subnet, or you can use an Ethernet crossover cable to connect the
CVS-1450 device directly to the development computer.
NO APP Switch
To prevent the CVS-1450 device from automatically running VIs at
startup, move the NO APP switch to the ON position and reset the
CVS-1450 device. If the CVS-1450 device becomes inaccessible because
of a startup program, enable the NO APP switch and reset the CVS-1450
device.
Enable this switch to prevent the CVS-1450 device default startup program
or Vision Builder AI from running at startup.
USER 1 Switch (LabVIEW Real-Time Module Users)
The USER 1 switch is user-configurable and has no default functionality.
You can use the RT Read Switch VI to read the USER 1 switch state and
perform a custom action based on the current switch state position.