Omron CPM1A Network Card User Manual


 
!
5Application Precautions
xiv
Always connect to a class-3 ground (to 100 or less) when installing the Units.
Not connecting to a class-3 ground may result in electric shock.
Always turn off the power supply to the PC before attempting any of the follow-
ing. Not turning off the power supply may result in malfunction or electric
shock.
Mounting or dismounting I/O Units, CPU Units, or any other Units.
Assembling the Units.
Connecting or wiring the cables.
Connecting or disconnecting the connectors.
Caution Failure to abide by the following precautions could lead to faulty operation of the
PC or the system, or could damage the PC or PC Units. Always heed these pre-
cautions.
Fail-safe measures must be taken by the customer to ensure safety in the
event of incorrect, missing, or abnormal signals caused by broken signal lines,
momentary power interruptions, or other causes.
Construct a control circuit so that power supply for the I/O circuits does not
come ON before power supply for the Unit. If power supply for the I/O circuits
comes ON before power supply for the Unit, normal operation may be tempo-
rarily interrupted.
If the operating mode is changed from RUN or MONITOR mode to PROGRAM
mode, with the IOM Hold Bit ON, the output will hold the most recent status. In
such a case, ensure that the external load does not exceed specifications. (If
operation is stopped because of an operation error (including FALS instruc-
tions), the values in the internal memory of the CPU Unit will be saved, but the
outputs will all turn OFF.)
Always use the power supply voltage specified in the operation manuals. An
incorrect voltage may result in malfunction or burning.
Take appropriate measures to ensure that the specified power with the rated
voltage and frequency is supplied. Be particularly careful in places where the
power supply is unstable. An incorrect power supply may result in malfunction.
Install external breakers and take other safety measures against short-circuit-
ing in external wiring. Insufficient safety measures against short-circuiting may
result in burning.
Do not apply voltages to the Input Units in excess of the rated input voltage.
Excess voltages may result in burning.
Do not apply voltages or connect loads to the Output Units in excess of the
maximum switching capacity. Excess voltage or loads may result in burning.
Disconnect the functional ground terminal when performing withstand voltage
tests. Not disconnecting the functional ground terminal may result in burning.
Install the Unit properly as specified in the operation manual. Improper installa-
tion of the Unit may result in malfunction.
Be sure that all the mounting screws, terminal screws, and cable connector
screws are tightened to the torque specified in the relevant manuals. Incorrect
tightening torque may result in malfunction.
Be sure to attach the supplied labels when wiring in order to prevent wiring cut-
tings from entering in the Unit.
Remove the label after the completion of wiring to ensure proper heat dissipa-
tion. Leaving the label attached may result in malfunction.
Use crimp terminals for wiring. Do not connect bare stranded wires directly to
terminals. Connection of bare stranded wires may result in burning.
Double-check all the wiring before turning on the power supply. Incorrect wir-
ing may result in burning.