Omron CPM1A Network Card User Manual


 
!
32
2. DIP Switch
Sets the temperature unit (°C or °F), and the number of decimal places
used.
Number of decimal places used
OFF: Normal (0 or 1); ON: 2
Temperature unit
OFF: °C; ON: °F
ON
12
3. Rotary Switch
Sets the temperature range. Set the range in accordance with the specifica-
tions of the temperature sensor used.
CPM1A-TS001/002
Set value Thermocouple Range (°C) Range (°F)
0
K
200 to 1,300 300 to 2,300
1 0.0 to 500.0 0.0 to 900.0
2
J
100 to 850 100 to 1,500
3 0.0 to 400.0 0.0 to 750.0
4 to F --- Setting not possible
CPM1A-TS101/102
Set value Platinum resistance
thermometer
Range (°C) Range (°F)
0 Pt100 200.0 to 650.0 300.0 to 1,200.0
1 JPt100 200.0 to 650.0 300.0 to 1,200.0
2 to F --- Setting not possible
4. Expansion I/O Connecting Cable
Connects the Temperature Sensor Unit to the expansion connector on the
PCs CPU Unit, an Expansion I/O Unit, or another Expansion Unit. The cable
is connected to the Temperature Sensor Unit and cannot be removed.
Caution Do not touch the expansion I/O connecting cable while the power is being sup-
plied in order to prevent any malfunction due to static electricity.
5. Expansion Connector
Connects to an additional Expansion I/O Unit or another Expansion Unit.
Unit Components
Section 2-2