Omron CPM1A Network Card User Manual


 
77
The operating mode of the CPM1A when the power is turned ON depends upon
the PC Setup setting in DM 6600 and the Programming Consoles mode switch
setting if the Programming Console is connected.
PC Setup setting
(DM 6600)
Programming
Console connected
Programming Console not
connected
0000 The startup mode
determined by the
mode switch setting.
RUN mode if no Programming Device
is connected. PROGRAM mode if
another Programming Device is
connected.
0100 The startup mode is the same as the operating mode before
power was interrupted.
0200 PROGRAM mode
0201 MONITOR mode
0202 RUN mode
Note The default setting is 0000. If a Programming Console is not connected, the PC
will automatically enter RUN mode. Be sure that it is safe for the PC to operate
before turning on the PC without a Programming Console connected.
4-2-3 Connecting the Programming Console
Connect the Programming Consoles connecting cable to the CPM1As periph-
eral port, as shown below.
Panel Installation The C200H-PRO27-E Programming Console can be installed in a control panel
as shown in the following diagram. (The C200H-ATT01 Mounting Bracket is sold
separately.)
186
+1.1
0
92
+0.8
0
Mounting Bracket
Two screws
Panel thickness: 1.0 to 3.2 mm
Mounting hole dimensions
(DIN43700 standards)
Startup Operating Mode
Using a Programming Console
Section 4-2