Powerware 9155 Power Supply User Manual


 
UPS-Mounted Bypass Switch Installation
34
Powerware
®
9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
4. Determine your equipment’s grounding requirements according
to your local electrical code.
5. Verify that the UPS battery circuit breaker is in the OFF position
(see Figure 17).
ON
OFF
Battery Circuit Breaker
Figure 17. UPS with MBM Rear View
6. Punch two holes in the MBM/PDM conduit landing plate for the
input and output conduit using a Greenlee punch or similar
device.
7. Hardwire the input (TB10-1 through TB10-4) and output (TB10-5
through TB10-8) terminations for the MBM/PDM.
See Table 7 for specifications and Figure 18 for a detailed view
of the MBM/PDM terminal block.