Configuring the UPS for EBMs
To ensure maximum battery runtime, configure the UPS for the correct
number of EBMs:
1. Press any button on the front panel display to activate the menu
options.
2. Using the button, scroll to the Settings menu.
3. Press the button twice to select the User Settings menu.
4. Using the button, scroll to the Number of Battery Strings
option and press the
button.
5. Use the or arrow buttons to select the number of strings
according to your UPS configuration:
All 2-High UPS and EBM Cabinets*
Number of Strings
UPS + 1 EBM 6
UPS + 2 EBMs 10
UPS + 3 EBMs 14
UPS + 4 EBMs 18
All 3-High UPS and EBM Cabinets* Num ber of Strings
UPS + 1 EBM 10
UPS + 2 EBMs 16
UPS + 3 EBMs 22
*UPS-32 models contain 2 strings; EBM-64 models contain 4 strings.
UPS-64 models contain 4 strings; EBM-96 models contain 6 strings.
6. Press the button to save the setting.
7. Press the
ESC
button until the Eaton Powerware logo appears.