Table 17. Dimensions and Weights
Dimensions (H x W x D) Weight
2-High UPS
32.2× 12× 32 (81 × 30 × 81 cm)
352 lb (160 kg)
3-High UPS-32
47.8× 12× 32 (121.5 × 30 × 81 cm)
550 lb (250 kg)
3-High UPS-64
47.8× 12× 32 (121.5 × 30 × 81 cm)
590 lb (268 kg)
2-High EBM
32.2× 12× 30.3 (81 × 30 × 77 cm)
480 lb (218 kg)
3-High EBM
47.8× 12× 30.3 (121.5 × 30 × 77 cm)
710 lb (322 kg)
PDM (rear UPS mount)
16.5× 12× 7 (42 × 30 × 17.8 cm)
25 lb (11 kg)
MBM (rear UPS mount)
16.5× 12× 7 (42 × 30 × 17.8 cm)
18 lb (8 kg)
Table 18. Environmental and Safety Specifications
Operating Temperature
10°C to 40°C (50°F to 104°F)
Optimal battery performance: 25°C (77°F)
Transit Temperature
-25°C to 55°C ( -13°F to 131°F)
Storage Temperature
0°C to 25°C (32°F to 77°F)
Recommended battery storage: 59°F (15°C) to 77°F (25°C)
Ventilation
Front air intake, forced air, two fans, positive pressurization,
temperature UPS-monitored
Altitude
9,843 ft (3,000m) operating without derating
32,810 ft (10,000m) during transportation
Relative Humidity
5–95% noncondensing
Heat Dissipation
5582 BTU/hr maximum online
5294 BTU/hr maximum on battery
Audible Noise
<56 dBA at 1 meter distance, typical loads
<62 dBA for heavy load, high ambient or high altitude, on battery
Safety Conformance
NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3;
EN 55022 Class A (CISPR22 Class A) and IEC 60950; IEC 62040-1-1
Agency Markings
UL, cUL, CE, NOM-NYCE
EMC(ClassA)
IEC 62040-2, FCC Part 15, ICES-003, VCCI
Surges
IEEE/ANSI C62.41 Cat B3