Powerware 9155 Power Supply User Manual


 
Specifications
89
Powerware
®
9155 UPS (8–15 kVA) User’s Guide S 164201553 Rev D www.powerware.com
Table 20. Model Specifications (continued)
Model 10 kVA
Output Voltage (line–line)
200 220 240 208 220
Output Voltage (line–neutral)
100 110 120 120 127
Input Current*
57A 52A 48A 48A 45A
Output Current
50A 45A 42A 42A 39A
Output kVA (line–line loads)
10.0 10.0 10.0 8.7 8.7
Output kVA (line–neutral loads)
10.0 10.0 10.0 10.0 10.0
Output kW
9.0 9.0 9.0 9.0 9.0
Output Peak Current
110 110 110 110 110
Efficiency (minimum)
87% 87% 87% 87% 87%
Power Dissipation (BTU/hr)
4175 4175 4175 4175 4175
DC Voltage (supply)
192 192 192 192 192
Model 8 kVA
Output Voltage (line–line)
200 220 240 208 220
Output Voltage (line–neutral)
100 110 120 120 127
Input Current*
46A 42A 38A 38A 36A
Output Current
40A 36A 33A 33A 31A
Output kVA (line–line loads)
8.0 8.0 8.0 6.9 6.9
Output kVA (line–neutral loads)
8.0 8.0 8.0 8.0 8.0
Output kW
7.2 7.2 7.2 7.2 7.2
Output Peak Current
88 88 88 88 88
Efficiency (minimum)
87% 87% 87% 87% 87%
Power Dissipation (BTU/hr)
3300 3300 3300 3300 3300
DC Voltage (supply)
192 192 192 192 192
*Input current for the input isolation transformer is 4% higher than for the UPS.