Table 20. Model Specifications
Model 15 kVA
Output Voltage (line–line)
200 220 240 208 220
Output Voltage (line–neutral)
100 110 120 120 127
Input Current*
71A 71A 71A 71A 67A
Output Current
63A 63A 63A 63A 59A
Output kVA (line–line loads)
12.5 13.8 15.0 13.0 13.0
Output kVA (line–neutral loads)
12.5 13.8 15.0 15.0 15.0
Output kW
11.3 12.4 13.5 13.5 13.5
Output Peak Current
155 155 155 155 155
Efficiency (minimum)
88% 88% 88% 88% 88%
Power Dissipation (BTU/hr)
5582 5582 5582 5582 5582
DC Voltage (supply)
192 192 192 192 192
Model 12 kVA
Output Voltage (line–line)
200 220 240 208 220
Output Voltage (line–neutral)
100 110 120 120 127
Input Current*
68A 62A 57A 57A 54A
Output Current
60A 55A 50A 50A 47A
Output kVA (line–line loads)
12.0 12.0 12.0 10.4 10.4
Output kVA (line–neutral loads)
12.0 12.0 12.0 12.0 12.0
Output kW
10.8 10.8 10.8 10.8 10.8
Output Peak Current
132 132 132 132 132
Efficiency (minimum)
88% 88% 88% 88% 88%
Power Dissipation (BTU/hr)
4512 4512 4512 4512 4512
DC Voltage (supply)
192 192 192 192 192
*Input current for the input isolation transformer is 4% higher than for the UPS.