Toshiba 1600XP Power Supply User Manual


 
19
1600XP Series Installation and Operation Manual
10.8 Battery Test
The 1600XP allows the user to conduct automatic or manual battery tests as desired. The following
steps detail the battery test procedures.
Automatic Battery Test:
1. The Automatic Battery Test Procedure is performed only if it is enabled during startup.
2. Once the battery test is completed, Cmd 654 - Battery Test Condition Status is set to “Battery
Test Prohibited”. It will be re-enabled once timer Cmd 655 - Battery Test Frequency is reached.
Manual Battery Test:
The UPS must be in Online mode.
1. On the display, press the Monitor tab.
2. On the display, press the C&C key.
3. Use the Page (<< and >>) and Record (< and>) navigation keys to verify the following:
a. Cmd 653 - Enable Battery Test set to “Enable” to allow the battery test to be performed.
b. Cmd 655 - Battery Test Frequency should be set to “0” (Daily)
c. Cmd 654 - Battery Test Condition Status must read “Battery Test OK to perform”
d. Cmd 652 - Battery Test Startup must be set to “Disable”
NOTE: if any of the above commands has asterisks, “*”,enter (write) the correct entry for that param-
eter. The UPS must be fully powered down and restarted after changing the command parameters.
4. Navigate to Cmd 609 - Requested State and press the “BattTest” button on the display.
• If the test passes, the display returns to the Monitor screen.
• If the test fails, the display returns to the Monitor screen and displays BTSTFL in the warning
section at the bottom left of the display, and the Warning LED blinks until the fault is cleared.