Toshiba 1600XP Power Supply User Manual


 
B-23
1600XP Series Installation and Operation Manual
624 Enable Transfer to Bypass
while in Async mode
En Asyn Byp - - - R/W R/W 1: Enable When Disabled, the UPS will not prevent transfers to
bypass mode during periods when the frequencies are
out of synch.
0: Disable
1: Enable
625 Enable CVCF* En CVCF* - - - R/W R/W Constant Voltage, Constant Frequency Mode (Restart
Required)
0: Disable
1: Enable
626 CVCF Output Frequency CVCF Frequency* - - - R/W R/W 6000 500 or 600 Only. Other values will default to 500
Systems.
(Restart Required)
Units: 0.1 Hz
634 System Date UPS Date R/W R/W R/W R/W R/W Depends on which protocol is used.
SNMP serial link and CAN communication –
1st Byte -> Day of Week (1 = Sunday, 2 = Monday, …, 7
= Saturday)
2nd Byte -> Date
3rd Byte -> Month
4th Byte -> Year (without 2000)
Hyper terminal -> “DOW MM/DD/YYYY”
635 System Time UPS Time R/W R/W R/W R/W R/W Depends on which protocol is used.
SNMP serial link and CAN communication –
1st Byte -> Hour
2nd Byte -> Minute
3rd Byte -> Second
see the related document.
Hyper terminal -> “HH:MM:SS”
636 System Timestamp Timestamp R R R R R Current system timestamp (32 bits format)
637 Enable Inverter / Bypass
command from REYE
En Reye UPS Ctl R R/W R/W R/W R/W 1: Enabled RemotEye is allowed to switch UPS Inverter to/From
Bypass or not!
0: Diable
1: Enable
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark