1600XP Series Installation and Operation Manual
17. Screen Tab: Settings
The Parameter Table in Appendix B lists the 1600XP Settings parameters that can be viewed in the
MONITOR tab.
Example: The Settings parameter Batt Test Freq (Battery Test Frequency) can be viewed by USR (User)
level and above. However, only ADM (Administrators) and above can edit )change) the parameter value.
Each key displays a block of relevant command parameters:
Key: Cmd ID - (Range) Parameter type
• ID – (000-099) UPS specic information such as serial number, software versions, installation date.
• Input – (100-199) Input measured/calculated data such as input voltage, frequency, current, power,
over-/under- voltage settings.
• Output – (200-299) Output measured/calculated data such as output voltage, frequency, current,
power, over-/under- voltage settings.
• Bypass – (300-399) Bypass data such as conguration, voltage, current, power, OV detection level.
• DC Bus – (400-499) Data such as Total voltage, rated voltage, Positive and Negative bus voltages.
• Batt – (500-599) Battery voltage, charger status, total discharges, shutdown voltage.
• Ctrl/Cfg – (600-699) Control and conguration list system and battery temperatures, system status,
startup delay, auto-transfer window, restart mode.
• History – (700-799) History lists metrics like system operation time, total over loads, hi system temp.
• Disp/Reye – (800-849) Display specic parameters like Disp. Firmware version, sleep timer, buzzer
status, display calibration points, and RemotEye III settings.
(850-859) lists RemotEye III IP address, IP Mask, Status, Baud Rate, datalink status.