Toshiba 1600XP Power Supply User Manual


 
B-16
1600XP Series Installation and Operation Manual
538 Number of Batteries Detection
Gain
539 Number Batteries Detection
Offset
540 Number Batteries Detection
AD Amount
541 Battery Discharge Current
Gain
542 Battery Discharge Current
Offset
543 Battery Discharge Current AD
544 Charger Reference (Normal
Charging Mode)
Charger
Ref(Norm)
- - - R/W R/W 55 Range: 0 – 320
545 Low Batery Level Low Batt Level R R R/W R/W R/W 90 % of battery norminal voltage.
Range: 0 – 100
Units: %
546 Charger Overvoltage
Detection Delay
VChrgOV DeDelay R R R/W R/W R/W 60 (Restart Required)
Range: 0 – 360
Units: Sec
547 Calculated Low Battery Level
in Vdc
Cal LB Level R R R R R 0 Calculated from level setup Command 545.
Units: Vdc
548 Charger Reference
(Preventive Charging Mode)
Charger Ref(Prev) - - - R/W R/W 150 Range: 0 – 320
549 Present Charger Reference Charger Ref - - - R R 0 Presently plotting charger reference
550 Charger Overvoltage
Detection Level
CHRGOV DeLevel - - - R/W R/W 117 Range: 100 – 150
Units: %
551 Charger Overvoltage warning
detection delay
CHRGOV
WrnDeDelay
- - - R/W R/W 8 Range: 1 – 240
Units: 1/2 Cyc
552 Charger Overvoltage warning
recovery delay
CHRGOV
WrnReDelay
- - - R/W R/W 1 Range: 0 – 59
Units: Sec
553 Charger Overvoltage fault
detection delay
CHRGOV
FltDeDelay
- - - R/W R/W 1 Range: 1 – 120
Units: Min
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark