Toshiba 1600XP Power Supply User Manual


 
D4
1600XP Series Installation and Operation Manual
UPS RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
6 0.85 240 25.00 0.10 510 18 1 216 82
6 0.85 240 25.00 0.20 1020 18 1 216 48
6 0.85 240 25.00 0.30 1530 18 1 216 32
6 0.85 240 25.00 0.40 2040 18 1 216 22
6 0.85 240 25.00 0.50 2550 18 1 216 16
6 0.85 240 25.00 0.60 3060 18 1 216 13
6 0.85 240 25.00 0.70 3570 18 1 216 11
6 0.85 240 25.00 0.80 4080 18 1 216 9
6 0.85 240 25.00 0.90 4590 18 1 216 8
6 0.85 240 25.00 1.00 5100 18 1 216 7
UPS RUNTIME WITH INTERNAL BATTERIES AND 1 BATTERY CABINET @ .85pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
6 0.85 240 25.00 0.10 510 18 3 216 180
6 0.85 240 25.00 0.20 1020 18 3 216 120
6 0.85 240 25.00 0.30 1530 18 3 216 90
6 0.85 240 25.00 0.40 2040 18 3 216 72
6 0.85 240 25.00 0.50 2550 18 3 216 60
6 0.85 240 25.00 0.60 3060 18 3 216 51
6 0.85 240 25.00 0.70 3570 18 3 216 45
6 0.85 240 25.00 0.80 4080 18 3 216 40
6 0.85 240 25.00 0.90 4590 18 3 216 35
6 0.85 240 25.00 1.00 5100 18 3 216 30
UPS RUNTIME WITH INTERNAL BATTERIES AND 2 BATTERY CABINETS @ .85pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
6 0.85 240 25.00 0.10 510 18 5 216 300
6 0.85 240 25.00 0.20 1020 18 5 216 180
6 0.85 240 25.00 0.30 1530 18 5 216 135
6 0.85 240 25.00 0.40 2040 18 5 216 112
6 0.85 240 25.00 0.50 2550 18 5 216 90
6 0.85 240 25.00 0.60 3060 18 5 216 82
6 0.85 240 25.00 0.70 3570 18 5 216 70
6 0.85 240 25.00 0.80 4080 18 5 216 63
6 0.85 240 25.00 0.90 4590 18 5 216 55
6 0.85 240 25.00 1.00 5100 18 5 216 51