B-14
1600XP Series Installation and Operation Manual
503 Battery Discharge Current Discharge Current R R R R R 0 valid only when dischaging and zero for charged mode
504 Battery Capacity Battery Capacity R R/W R/W R/W R/W 0
505 Battery Runtime Battery Runtime R R R R R 400
506 Battery Charger Status Charger Status R R R R R 0 0 = Normal Charging
1 = Preventive Charging
2 = Stop Charging
507 Number of Battery Discharges Total Discharges R R/W R/W R/W R/W 0 Increment when backup mode more than 10 Sec long
508 Calculated Battery Shutdown
Voltage
Cal Battery Vsd R R R R R Calculated from manufacturer’s data sheet.
Units: Vdc
509 Battery Life Remaining Batt Life Remain R R/W R/W R/W R/W 43800 Range: 0 – 43800
Units: Hr
510 C Rate
511 Rated Battery AmpereHour Rated Ahr R R/W R/W R/W R/W 9 Battery capacity AmpereHour such as 7 AHr or 9 Ahr.
Range: 1 – 15
Units: Ahr
512 Number Battery In Series No Batt(Series) R R/W R/W R/W R/W 18 Range: 0 – 48
513 Number Battery in Parallel No Batt(Paral) R R/W R/W R/W R/W 1 Range: 0 – 24
514 Battery Installation Date Batt Ins Date R R/W R/W R/W R/W “20080101” YYYYMMDD
515 Battery Typeform
516 Battery Voltage Shutdown
Level
Batt SDown Level R R R/W R/W R/W 79 Percentage of norminal battery voltage.
Range: 0 – 120 Units: %
517 Floating Charge Voltage
518 Charging Prevention Voltage
519 Battery Charge Current
Switching Point
520 Battery Charge Current Limit
(Maximum)
521 Maximum Charge Voltage
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark