Toshiba 1600XP Power Supply User Manual


 
B-8
1600XP Series Installation and Operation Manual
225 Output Frequency
Slew Rate
Fo Slew Rate - - - R/W R/W 10 The smallest control amount to add or subtract from the
current output frequency. Ups converts to a correct value
of per cycle instead of per second.
Range: 1 – 30
Units: 0.1 Hz
226 Output Voltage Adjustment
(Total)
Vout Adjust R R/W R/W R/W R/W 0 End user’s manual adjustment for output voltage
if desired. 1 increment or decrement will give
approximately 1 Vrms output.
Range: -10 – 10
227 Output Current 100% Amount Iout 100% Amount - - - R/W R/W 250 Range: 0 – 1500
Units: dA
228 Output Overload Warning/
Fault Detection Level in
Percentage
OOL Delevel - - - R/W R/W 110 Range: 0 – 150
Units: %
229 Output Overload Warning/
Fault Detection Delay at 125%
@ 25
0
C
OOL DeDelay - - - R/W R/W 30 Range: 0 – 300
Units: Sec
230 Output Overload Warning
Recovery Level in Percentage
OOL ReLevel - - - R/W R/W 105 Range: 90 – 120
Units: %
231 Output Overload Warning
Recovery Delay
OOL ReDelay - - - R/W R/W 160 Range: 120 – 1000
Units: Sec
232 Output Voltage
Compensation
Vout Comp. Step - - - R/W R/W 20 Output voltage will be compensated according to this
setup and current percentage.
Range: 1 – 200
Units: 1 Cyc
233 Output Voltage Gain
(Phase A or Total)
Vout Gain - - - R/W R/W 7987 Used this value to convert AD value to actual unit.
Range: 1 – 32767
234 Output Voltage Offset
(Phase A or Total)
Vout Offset - - - R/W R/W 0 Feedback Offset adjustment due to hardware
components and software AD converter’s offset.
Range: -32767 – 32767
235 Output Voltage AD Amount
(Phase A or Total)
Vout AD - - - R R 0 AD summation of 16 samples per half cycle.
242 Output Current Gain
(Phase A or Total)
Iout Gain - - - R/W R/W 1131 Rated at 240 V output voltage.
Used this value to convert AD value to actual unit.
Range: 1 – 32767