B-15
1600XP Series Installation and Operation Manual
522
1
Enable External Battery
Cabinet 1
Enable BC1 R R/W R/W R/W R/W 0
523
1
Enable External Battery
Cabinet 1
Enable BC2 R R/W R/W R/W R/W 0
524 External Batt Cabinet
Installation Status
SbatEx - - - R/W R/W 0 0: Uninstalled
1: Installed
525 External Batt Cabinet Number
of Batteries in Series
No Ex Bat(Series) R R/W R/W R/W R/W 0 Range: 0 – 48
526 External Battery Cabinet
Number of Batteries in Parallel
No Ex Bat(Paral) R R/W R/W R/W R/W 0 Range: 0 – 24
527 External Battery Cabinet
Rated Battery AmpereHour
Ex Batt Rated Ahr R R/W R/W R/W R/W 0 Range: 0 – 12
Units: Ahr
528 External Battery Cabinet
Rated Battery Discharge C
Rate
Ex Batt C Rate R R/W R/W R/W R/W 0 Range: 0 – 12
Units: C
529 External Battery Cabinet
Installation Date
Ext Batt Ins Date R R/W R/W R/W R/W “20080101” Format: YYYYMMDD
530 External Battery Cabinet
Typeform/Description
531 External Battery Cabinet
Battery Voltage Shutdown
Level
532 Battery Voltage Gain Vbat Gain - - - R/W R/W 8298 Used this value to convert AD value to actual unit.
Range: 1 – 32767
533 Battery Voltage Offset Vbat Offset - - - R/W R/W 0 Feedback Offset adjustment due to hardware
components and software AD converter’s offset.
Range: -32768 – 32767
534 Battery Voltage AD Amount Vbat AD - - - R R 0 AD summation of 16 samples per half cycle.
535 Battery Current Gain
536 Battery Current Offset
537 Battery Current AD Amount
Item Brief Description
Description
On lCD
U A D
Svc/