B-9
1600XP Series Installation and Operation Manual
243 Output Current Offset
(Phase A or Total)
Iout Offset - - - R/W R/W 0 Feedback Offset adjustment due to hardware
components and software AD converter’s offset.
Range: -32767 – 32767
244 Output Current AD Amount
(Phase A or Total)
Iout AD - - - R R 0 AD summation of 16 samples per half cycle.
251 Output Voltage Reference
Phase Adjustment for 60 Hz*
Vref PhAdj 60 Hz* - - - R/W R/W -8 Time delay adjustment to sync the actual phase of
output and plotting. (Restart Required).
Range -64 – 64
252 Phase Lock Loop Controller’s
Propotional Gain
Pll Gp - - - - R/W 4 Range: 0 – 128
Units: /256
253 Phase Lock Loop Controller’s
Integral Gain
Pll Gi - - - - R/W 2 Range: 0 – 128
Units: /256
254 Output Voltage Reference
Amplitute
Vref Amplitute - - - R/W R/W 246 Calibrated at no Load output voltage.
Range: 0 – 300
Units: /128
255 Timer 3 Offset Remainder T3 Offset Remain - - - - R/W 350 Range: 0 – 1500
Units: /128
256 DC to AC Efciency DC-AC Efciency - - - R/W R/W 81 Range: 0 – 100
Units: %
257 Frequency Syn to Asyn
Warning Detection Delay
Freq Asyn
DeDelay
- - - - R/W 4 Range: 0 – 300
Units: 1 Cyc
258 Frequency Asyn to Syn
Recovery Delay
Freq Syn ReDelay - - - - R/W 8 Range: 0 – 300
Units: 1 Cyc
259 Phase Syn to Asyn Warning
Detection Delay
Ph. ASyn DeDelay - - - - R/W 4 Range: 0 – 300
Units: 1 Cyc
260 Phase Asyn to Syn Recovery
Delay
Ph. Syn ReDelay - - - - R/W 8 Range: 0 – 300
Units: 1 Cyc
261 Rated Power Factor Rated PFactor R R R R/W R/W 85 Calculated from typeform and rated voltage.
Range: 0 – 120
Units: dd
262 AC to AC Efciency AC-AC Efciency - - - R/W R/W 85 Range: 0 – 100
Units: %
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark