Toshiba 1600XP Power Supply User Manual


 
B-24
1600XP Series Installation and Operation Manual
639 Enable Startup Delay* En Startup Delay* R R/W R/W R/W R/W 0: Disabled Delay Timer enable or disable during Normal startup
(Not Shutdown by battery or Not LAN Shutdown),
(Restart Required)
0: Disable
1: Enable
640 Startup Mode (Bypass or
Inverter)
Startup Mode* R R/W R/W R/W R/W 0: Bypass The Operation Mode into which the UPS will transition
at expiration of the Start Up Delay timer (when enabled).
(Restart Required)
0: Bypass
1: Online
Any other value besides 0 and 1 will be considered
Shutdown
641 Startup Delay Timer Value Startup Delay* R R/W R/W R/W R/W 0 (Restart Required)
Range: 0 – 800
Units: Sec
644 Remote ‘Shutdown’ Contact
State
Remote SD Status R R R R R 0 0: Open (deactivated)
1: Closed (activated)
645 Remote ‘Shutdown’ Contact
Mode Selection
Mode of Rmt
SDown
R R/W R/W R/W R/W 0: Bypass 0: Bypass state
1: Shutdown state while contact is closed. Return to
previous state when contact is open.
646 Enable LAN Shutdown En DCntct LANSD R R/W R/W R/W R/W 1: Enable
647 LAN Shutdown Signal
Permitted Time Window
DCntct LANSD
Wndw
R R/W R/W R/W R/W 600 Range: 0 – 800 Units: Sec
648 Remote ‘On Batteries’ Delay
Timer
BK DContact
Delay
R R/W R/W R/W R/W 10 Delay timer between actual event occurrence and dry
contact closure to signal external devices of the event.
Range: 0 – 800
Units: Sec
649 Remote ‘Low Battery’ Delay
Timer
LB DContact Delay R R/W R/W R/W R/W 0 Delay timer between actual event occurrence and dry
contact closure to signal external devices of the event.
Range: 0 – 800
Units: Sec
652 Enable Battery Test on UPS
Startup
En Batt Test Sup* R R/W R/W R/W R/W 0: Disabled Forces a battery test when UPS starts after normal
shutdown. (Restart Required)
0: Disable
1: Enable
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark