B-26
1600XP Series Installation and Operation Manual
681 SNMP Port Mode SNMP Port Mode - - - R/W R/W 1: Protocol Rqrd. 0: Terminal mode (no handshake, no error check)
1: Toshiba UPS Communication Protocol 2-0 mode
682 Fault Clear counter Flt Cleared Cnt R R R R/W R/W 0
683 Fault Clear Mask Low Flt Clear Mask Lo - - - R/W R/W 0x0000 Range: 0x0000 – 0xFFFF
Units: Hex
684 Fault Clear Mask High Flt Clear Mask Hi - - - R/W R/W 0x0000 Range: 0x0000 – 0xFFFF
Units: Hex
685 Total Faults Allowed Total Flt Allowed - - - R/W R/W 10 Range: 0 – 255
686 Fault Disable Time Flt Dis Time - - - R/W R/W 10 Range: 0 – 255
Units: Min
687 Fault Disable Countdown
Timer
Flt Dis Cdown Tmr R R R R R 0 Units: Sec
693 Remote Shutdown inverted
logic
Invert Rmt SDown R R/W R/W R/W R/W 0 0: Not Inverted
1: Inverted
694 Reset Hardware Fault Latch Reset HW Fault - - - R/W R/W 0 0 = Do Nothing
1 = Reset Fault Hardware
695 Restart Mode* Restart Mode* R R/W R/W R/W R/W 1 0: Bypass
1: Online
Any other value besides 0 and 1 will be considered
Shutdown
(Restart Required)
696 Software Mishap restart mode SWMishap Mrstrt - - - R/W R/W 1
697 Enable DMX En DMX - R/W R/W R/W R/W 0
701 System Operation Time System Op Time R R R R/W R/W 0 Units: Sec
702 Inverter Operation Time Inverter Op Time R R R R/W R/W 0 Units: Sec
703 Backup Operation Time Backup Op Time R R R R/W R/W 0 Units: Sec
704 UPS Lifetime Remaining UPS Lifetime R R R R/W R/W 61320 Range: 0 – 61320
Units: Hrs
705 Peak (Highest) system
Temperature
Hi System Temp R R R R/W R/W 0 Units: °C
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark