UPS RUNTIME WITH ONLY INTERNAL BATTERIES @ .70pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
6 0.7 240 25.00 0.10 420 18 1 216 90
6 0.7 240 25.00 0.20 840 18 1 216 55
6 0.7 240 25.00 0.30 1260 18 1 216 40
6 0.7 240 25.00 0.40 1680 18 1 216 28
6 0.7 240 25.00 0.50 2100 18 1 216 21
6 0.7 240 25.00 0.60 2520 18 1 216 16
6 0.7 240 25.00 0.70 2940 18 1 216 14
6 0.7 240 25.00 0.80 3360 18 1 216 11
6 0.7 240 25.00 0.90 3780 18 1 216 10
6 0.7 240 25.00 1.00 4200 18 1 216 7
UPS RUNTIME WITH INTERNAL BATTERIES AND 1 BATTERY CABINET @ .70pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
6 0.7 240 25.00 0.10 420 18 3 216 180
6 0.7 240 25.00 0.20 840 18 3 216 135
6 0.7 240 25.00 0.30 1260 18 3 216 105
6 0.7 240 25.00 0.40 1680 18 3 216 86
6 0.7 240 25.00 0.50 2100 18 3 216 70
6 0.7 240 25.00 0.60 2520 18 3 216 60
6 0.7 240 25.00 0.70 2940 18 3 216 53
6 0.7 240 25.00 0.80 3360 18 3 216 46
6 0.7 240 25.00 0.90 3780 18 3 216 43
6 0.7 240 25.00 1.00 4200 18 3 216 38
UPS RUNTIME WITH INTERNAL BATTERIES AND 2 BATTERY CABINETS @ .70pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
6 0.7 240 25.00 0.10 420 18 5 216 300
6 0.7 240 25.00 0.20 840 18 5 216 180
6 0.7 240 25.00 0.30 1260 18 5 216 150
6 0.7 240 25.00 0.40 1680 18 5 216 120
6 0.7 240 25.00 0.50 2100 18 5 216 105
6 0.7 240 25.00 0.60 2520 18 5 216 90
6 0.7 240 25.00 0.70 2940 18 5 216 82
6 0.7 240 25.00 0.80 3360 18 5 216 72
6 0.7 240 25.00 0.90 3780 18 5 216 65
6 0.7 240 25.00 1.00 4200 18 5 216 60