19.2 (Optional) External Maintenance Bypass
Wiring
The following connections must be made to the Utility Panel and the Load Panel. The Main UPS output is
located on the terminal block on the back of the UPS. (TB-4(X1) and TB-7(X3) 240 VAC.)
See the application instructions included with the External Maintenance Bypass Unit for wiring details.
Do NOT use two legs of a three phase, 208/120V utility to feed the 1600XP, as shown below, if an ex-
ternal maintenance bypass is being used. The phase shift between the output of the UPS and the utility
feed to the bypass could interrupt the power to to load.
DO NOT USE 3-PHASE INPUT WHEN USING AN EXTERNAL MAINTENANCE BYPASS