Toshiba 1600XP Power Supply User Manual


 
B-10
1600XP Series Installation and Operation Manual
264 OutputTo NoOutput or
NoOutput to Output mode
Gates transfer timing at Vout*
Gates Xfer Vout* - - - - R/W 75 Output to no output or no output to output mode transfer
timing in degree. Other mode, trasfer timing is at zero
cross (Restart Required).
Range: 60 – 300
Units: 1 Cyc
265 Overload Detection Disable
Delay
OL Disable Delay - - - - R/W 8 Range: 0 – 16
Units: 1/2 cyc
266 Present plotting output voltage
reference amplitute
Present VoutRef - - - R R 0 uC generated reference amplitute.
267 Output Voltage Reference
Phase Adjustment for 50 Hz*
Vref PhAdj 50 Hz* - - - R/W R/W -7 Range: -64 – 64
268 Output Power Limited by
Converter (1) / Transformer (0)
Cnv/Xfmer Lmt - - - R/W R/W 0 power calculation is limited by
1 = input converter limited
0 = output transformer limited (default)
269 Output Voltage before
Tranformer Compensation
Vout B4 Comp. - - - R/W R/W 0 Units: V
270 Output Current before
Tranformer Compensation
Iout B4 Comp. - - - R/W R/W 0 Units: dA
271 Inverter Mode A CompensationComp. Ainv - - - R/W R/W 2 Range: 0 – 512
Units: /128
272 Inverter Mode B
Compensation
Comp. Binv - - - R/W R/W 10 Range: 0 – 512
Units: /128
273 Inverter Mode C
Compensation
Comp. Cinv - - - R/W R/W 0 Range: 0 – 512
Units: /128
274 Bypass Mode A CompensationComp. Abyp - - - R/W R/W 3 Range: 0 – 512
Units: /128
275 Bypass Mode B CompensationComp. Bbyp - - - R/W R/W 7 Range: 0 – 512
Units: /128
276 Bypass Mode C
Compensation
Comp. Cbyp - - - R/W R/W 1 Range: 0 – 512
Units: /128
277 Overload Time Window OL Time Wndw - - - R/W R/W 10 Range: 0 – 30
Units: min
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark