Toshiba 1600XP Power Supply User Manual


 
B-11
1600XP Series Installation and Operation Manual
278 Rated Output Primary
Transformer
Rated OutXfmer(P) - - - R/W R/W 230 Range: 200 – 300
Units: V
279 50 Hz Derating 50Hz Derating - - - R/W R/W 100 Range: 50 – 150
Units: %
280 60 Hz Derating 60Hz Derating - - - R/W R/W 100 Range: 50 – 150
Units: %
301 Bypass Power Supply
Conguration
Bypass Cong R R R R R Always, the same as input conguration
0 = unknown (>= 0, < 199)
1 = 200V – 60Hz (>= 200, <207)
2 = 200V – 50Hz (>= 200, <207)
3 = 208V – 60Hz (>= 208, < 229)
4 = 208V – 50Hz (>= 208, < 229)
5 = 230V – 60Hz (>= 230, < 239)
6 = 230V – 50Hz (>= 230, < 239)
7 = 240V – 60Hz (>= 240, < 32767)
8 = 240V – 50Hz ( >= 240, < 32767)
9 = 220V – 60Hz
10 = 220V – 50Hz
11 = 120V – 60Hz
12 = 120V – 50Hz
These numbers are stored in recording features
302 Number of Bypass phases No Of Bypass Line R R R R/W R/W 1
303 Bypass Voltage
(Total)
Bypass Voltage R R R R R 0 Always the same as input voltage.
Units: Vrms
304 Bypass Current
(Total)
Bypass Current R R R R R 0 Only valid at bypass mode and zero for other ups mode.
Units: Irms
305 Bypass Frequency
(Total)
Bypass Frequency R R R R R 0 Always the same as input frequency.
Units: 0.1 Hz
307 Bypass Apparent Power (VA) Bypass Power(VA) R R R R R 0 Only valid at bypass mode and zero for other ups mode.
Units: VA
315 Bypass Undervoltage Warning
Detection Level
VBypUV DeLevel R R R R/W R/W 62 Range: 0 – 100
Units: %
316 Bypass Undervoltage Warning
Recovery Level
VBypUV ReLevel R R R R/W R/W 66 Range: 0 – 100
Units: %
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark