B-7
1600XP Series Installation and Operation Manual
206 Output Active Power (W) Output Power(W) R R R R R 0 -1 if output active power can not be calculated (Bypass
Mode).
Units: W
207 Output Apparent Power (VA) Output Power(VA) R R R R R 0 Units: VA
209 Output Load Percentage
(Total)
Output Load (%) R R R R R 0 Dened as output current percentage or output active
power whichever higher.
Units: %
215 Rated Output Voltage
(Total)
Rated Vout R R/W R/W R/W R/W 240 Must be non-zero value. Undened behavior if diveded
by zero.
Range: 1 – 300
Units: Vrms
216 Rated Output Current
(Total)
Rated Iout R R R R/W R/W 250 Calculated from typeform and not writtable.
Range: 0 – 1500
Units: 0.1 Arms
217 Rated Output Frequency
(Total)
Rated Fout R R R R R 0 Determined according to DIP switch or EEPROM setup.
Units: 0.1 Hz
218 Rated Output Active Power Rated Pout(W) R R R R R 0 UPS calculates at the startup according to typeform,
efciency and rated power factor.
Units: W
219 Rated Output Apparent Power Rated Pout(VA) R R R R R 0 UPS calculates at the startup according to typeform,
efciency and rated power factor.
Units: VA
220 Output Under Voltage Fault
Detection Level
VOUV DeLevel R R R R/W R/W 90 Output Under Voltage Detection level in percentage of
Rated Output Voltage.
Range: 0 – 100
Units: %
222 Output Overvoltage Fault
Level
VOOV DeLevel R R R R/W R/W 110 Output Over Voltage Detection level in percentage of
Rated Output Voltage.
Range: 100 – 150
Units: %
224 Output Frequency
Synchronization Range
Fo Syn Window R R R R/W R/W 10 Output voltage will follow input voltage if the difference of
input and output are within this value (according to slew
rate, of course).
Range: 1 – 30
Units: 0.1 Hz
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark