Toshiba 1600XP Power Supply User Manual


 
D12
1600XP Series Installation and Operation Manual
UPS RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
18 0.85 240 75.00 0.10 1530 24 2 288 90
18 0.85 240 75.00 0.20 3060 24 2 288 48
18 0.85 240 75.00 0.30 4590 24 2 288 31
18 0.85 240 75.00 0.40 6120 24 2 288 21
18 0.85 240 75.00 0.50 7650 24 2 288 16
18 0.85 240 75.00 0.60 9180 24 2 288 12
18 0.85 240 75.00 0.70 10710 24 2 288 10
18 0.85 240 75.00 0.80 12240 24 2 288 9
18 0.85 240 75.00 0.90 13770 24 2 288 7
18 0.85 240 75.00 1.00 15300 24 2 288 5
UPS RUNTIME WITH INTERNAL BATTERIES AND 1 BATTERY CABINET @ .85pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
18 0.85 240 75.00 0.10 1530 24 5 288 240
18 0.85 240 75.00 0.20 3060 24 5 288 112
18 0.85 240 75.00 0.30 4590 24 5 288 82
18 0.85 240 75.00 0.40 6120 24 5 288 60
18 0.85 240 75.00 0.50 7650 24 5 288 50
18 0.85 240 75.00 0.60 9180 24 5 288 42
18 0.85 240 75.00 0.70 10710 24 5 288 35
18 0.85 240 75.00 0.80 12240 24 5 288 28
18 0.85 240 75.00 0.90 13770 24 5 288 24
18 0.85 240 75.00 1.00 15300 24 5 288 21
UPS RUNTIME WITH INTERNAL BATTERIES AND 2 BATTERY CABINETS @ .85pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
18 0.85 240 75.00 0.10 1530 24 8 288 300
18 0.85 240 75.00 0.20 3060 24 8 288 165
18 0.85 240 75.00 0.30 4590 24 8 288 120
18 0.85 240 75.00 0.40 6120 24 8 288 90
18 0.85 240 75.00 0.50 7650 24 8 288 78
18 0.85 240 75.00 0.60 9180 24 8 288 65
18 0.85 240 75.00 0.70 10710 24 8 288 55
18 0.85 240 75.00 0.80 12240 24 8 288 50
18 0.85 240 75.00 0.90 13770 24 8 288 45
18 0.85 240 75.00 1.00 15300 24 8 288 40