Toshiba 1600XP Power Supply User Manual


 
B-12
1600XP Series Installation and Operation Manual
317 Bypass Overvoltage Warning
Detection Level
VBypOV DeLevel R R R R/W R/W 284 Range: 0 – 500
Units: V
318 Bypass Overvoltage Warning
Recovery Level
VBypOV ReLevel R R R R/W R/W 274 Range: 0 – 500
Units: V
320 Bypass Overload Fault
Detection Delay at 125% @
25
0
C
BypOL DeDelay - - - R/W R/W 600 Range: 0 – 1000
Units: sec
339 Bypass Undervoltage
Detection Delay
VBypUV DeDelay - - - - R/W 1 Range: 0 – 600
Units: 1/2 cyc
340 Bypass Undervoltage
Recovery Delay
VBypUV ReDelay - - - - R/W 128 Range: 0 – 600
Units: 1/2 cyc
341 Bypass Overvoltage Detection
Delay
VBypOV DeDelay - - - - R/W 1 Range: 0 – 600
Units: 1/2 cyc
342 Bypass Overvoltage Recovery
Delay
VBypOV ReDelay - - - - R/W 128 Range: 0 – 600
Units: 1/2 cyc
343 Bypass Frequency Error
Detection Delay
FBypERR
DeDelay
- - - - R/W 4 Range: 0 – 300
Units: cyc
344 Bypass Undervoltage
Detection Delay
FBypERR
ReDelay
- - - - R/W 128 Range: 0 – 300
Units: cyc
401 DC Bus Voltage
(Total)
DC Bus Total R R R R R 0 Units: Vdc
402 DC Bus Voltage
(Positive)
DC Bus Positive R R R R R 0 Units: Vdc
403 DC Bus Voltage
(Negative)
DC Bus Negative R R R R R 0 Units: Vdc
404 Rated DC Bus Voltage Rated DC Bus R R R R/W R/W 770 Range: 200 – 800
Units: Vdc
405 DC Bus Overvoltage Fault
Detection Level Percentage
DCOV DeLevel - - - R/W R/W 110 Range: 80 – 120
Units: %
406 DC Bus Undervoltage Fault
Detection Level Percentage
DCUV DeLevel - - - R/W R/W 83 Range: 0 – 100
Units: %
409 DC Bus Imbalance Fault
Detection Level Percentage
DCIB DeLevel - - - R/W R/W 11 Range: 0 – 50
Units: %
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark