Toshiba 1600XP Power Supply User Manual


 
F1
1600XP Series Installation and Operation Manual
Appendix F: External Battery Cabinets (Non-Matching)
Non-matching battery cabinets are available in a variety of sizes to match your back-up needs. Table F-1
lists the estimated backup time for each UPS model battery cabinet selections available for each 1600XP
model.
Each of the battery cabinets listed below comes with 10 foot long DC power cables with UPS-specic
keyed Anderson plugs.
TABLE F-1 - ESTIMATED BACKUP TIMES AT RATED LOAD FOR ONE (1) NON-MATCHING BATTERY CABINET
Battery
Cabinet
3.6kVA
Runtime
(Weight)
6kVA
Runtime
(Weight)
8kVA
Runtime
(Weight)
10kVA
Runtime
(Weight)
14kVA
Runtime
(Weight)
18kVA
Runtime
(Weight)
22kVA
Runtime
(Weight)
25T 150 min. (1160 lbs)
210 min. (1400 lbs)
270 min. (1775 lbs)
120 min.
(1520 lbs)
120 min.
(1880 lbs)
120 min.
(2360 lbs)
(See
Note)
60 min.
(2360 lbs)
(See
Note)
39T (N/A) 240 min.
(2523 lbs)
240 min.
(3183 lbs)
180 min.
(3183 lbs)
120 min.
(3183 lbs)
(See
Note)
60 min.
(3168 lbs)
Note: Additional runtime can be achieved by adding additional battery cabinets. Contact your Toshiba representative
for details.
TABLE F-2 - NON-MATCHING BATTERY CABINET DIMENSIONS
Battery
Cabinet
Width
Depth Height
25T 29 in. 31.5 in 59 in.
39T 36 in. 29.5 in. 70.7 in.