Toshiba 1600XP Power Supply User Manual


 
D13
1600XP Series Installation and Operation Manual
22kVA - UHG3G2L220C61xxx
UPS RUNTIME WITH ONLY INTERNAL BATTERIES @ .70pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
22 0.7 240 91.67 0.10 1540 24 2 288 90
22 0.7 240 91.67 0.20 3080 24 2 288 48
22 0.7 240 91.67 0.30 4620 24 2 288 30
22 0.7 240 91.67 0.40 6160 24 2 288 21
22 0.7 240 91.67 0.50 7700 24 2 288 16
22 0.7 240 91.67 0.60 9240 24 2 288 12
22 0.7 240 91.67 0.70 10780 24 2 288 10
22 0.7 240 91.67 0.80 12320 24 2 288 8
22 0.7 240 91.67 0.90 13860 24 2 288 7
22 0.7 240 91.67 1.00 15400 24 2 288 5
UPS RUNTIME WITH INTERNAL BATTERIES AND 1 BATTERY CABINET @ .70pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
22 0.7 240 91.67 0.10 1540 24 5 288 240
22 0.7 240 91.67 0.20 3080 24 5 288 112
22 0.7 240 91.67 0.30 4620 24 5 288 82
22 0.7 240 91.67 0.40 6160 24 5 288 60
22 0.7 240 91.67 0.50 7700 24 5 288 50
22 0.7 240 91.67 0.60 9240 24 5 288 42
22 0.7 240 91.67 0.70 10780 24 5 288 35
22 0.7 240 91.67 0.80 12320 24 5 288 28
22 0.7 240 91.67 0.90 13860 24 5 288 24
22 0.7 240 91.67 1.00 15400 24 5 288 21
UPS RUNTIME WITH INTERNAL BATTERIES AND 2 BATTERY CABINETS @ .70pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
22 0.7 240 91.67 0.10 1540 24 8 288 300
22 0.7 240 91.67 0.20 3080 24 8 288 165
22 0.7 240 91.67 0.30 4620 24 8 288 120
22 0.7 240 91.67 0.40 6160 24 8 288 90
22 0.7 240 91.67 0.50 7700 24 8 288 78
22 0.7 240 91.67 0.60 9240 24 8 288 65
22 0.7 240 91.67 0.70 10780 24 8 288 55
22 0.7 240 91.67 0.80 12320 24 8 288 50
22 0.7 240 91.67 0.90 13860 24 8 288 44
22 0.7 240 91.67 1.00 15400 24 8 288 40