Toshiba 1600XP Power Supply User Manual


 
B-5
1600XP Series Installation and Operation Manual
127 Input Current 100% Amount Iin 100% Amount - - - R/W R/W 250 Range: 1 – 1500
Units: dA
128 Input Current Reference
Phase Adjustment*
Iref Phase Adj* - - - R/W R/W 14800 Time delay adjustment to sync the phase of input voltage
and current due to hardware and software delay.
(Restart Required)
Range: 0 – 32767
Units: duS
129 Input Undervoltage Warning
Detection Delay
VIUV DeDelay - - - - R/W 1 Input Under Voltage Error detection delay in
consecutively.
Range: 0 – 600
Units: 1/2 Cyc
130 Input Undervoltage Warning
Recovery Delay
VIUV ReDelay - - - - R/W 8 Input Over Voltage Error recovery delay in consecutively
Range: 0 – 600
Units: 1/2 Cyc
131 Input Overvoltage Warning
Detection Delay
VIOV DeDelay - - - - R/W 1 Input Under Voltage Error detection delay in
consecutively
Range: 0 – 600
Units: 1/2 Cyc
132 Input Overvoltage Warning
Recovery Delay
VIOV ReDelay - - - - R/W 8 Input Over Voltage Error recovery delay in consecutively
Range: 0 – 600
Units: 1/2 Cyc
133 Input Frequency Warning
Detection Delay
FIERR DeDelay - - - - R/W 4 Input Frequency Error detection delay in consecutively
Range: 0 – 300
Units: 1 Cyc
134 Input Frequency Warning
Recovery Delay
FIERR ReDelay - - - - R/W 8 Input Frequency Error recovery delay in consecutively
Range: 0 – 300
Units: 1 Cyc
135 Input Voltage in percentage Input Voltage(%) R R R R R 0 Ratio of input voltage to rated input voltage.
Units: %
136 Input Current in percentage Input Current(%) R R R R R 0 Ratio of input current to rated input current.
Units: %
137 Calculated Input Undervoltage
Warning Detection Level
VIUV DeLevel R R R R R 0 UPS calculates input voltage detection level according
to output power (W) percentage, Gradient, Section and
Rated values.
Units: V
Item Brief Description
Description
On lCD
U A D
Svc/
QC
F Default Remark