Toshiba 1600XP Power Supply User Manual


 
B-6
1600XP Series Installation and Operation Manual
138 Calculated Input Undervoltage
Warning Recovery Level
VIUV ReLevel R R R R R 0 UPS Calculates input voltage recovery level according to
detection level and hystersis.
Units: V
139 Rated Active Input Power (W) Rated InPower(W) R R R R R 0 UPS calculates at the startup according to typeform,
efciency and rated power factor.
Units: W
141 Input Frequency Setup in
Case of Input Frequency
Detection Error
Freq on FIERR* R R/W R/W R/W R/W 6000 This frequency setup is used after UPS could not
determine input frequency in 3 Seconds. Then UPS
determine output frequency according to DIP Switch or
EEPROM setup.
Range: 500 – 600
Units: dHz
201 Output Power Supply
Conguration
Output Cong R R R R R 0 = unknown (>= 0, < 199)
1 = 200V – 60Hz (>= 200, <207)
2 = 200V – 50Hz (>= 200, <207)
3 = 208V – 60Hz (>= 208, < 229)
4 = 208V – 50Hz (>= 208, < 229)
5 = 230V – 60Hz (>= 230, < 239)
6 = 230V – 50Hz (>= 230, < 239)
7 = 240V – 60Hz (>= 240, < 32767)
8 = 240V – 50Hz ( >= 240, < 32767)
9 = 220V – 60Hz
10 = 220V – 50Hz
11 = 120V – 60Hz
12 = 120V – 50Hz
These numbers are stored in recording features. Range:
0 – 15
202 Number of Output Lines No of Output Line R R R R/W R/W 1 Range: 1 – 2
203 Output Voltage
(Total)
Output Voltage R R R R R 0 Units: Vrms
204 Output Current
(Total)
Output Current R R R R R 0 Units: 0.1 Arms
205 Output Frequency
(Total)
Output Frequency R R R R R 0 Calculated only at Bypass mode and inverter mode. Set
to zero for other modes.
Units: 0.1 Hz
Item Brief Description
Description
On lCD
U A D
Svc/
QC