37
1600XP Series Installation and Operation Manual
17.1 Changing UPS Parameter Settings
Press the parameter to be changed and the display will open with an appropriate data entry screen.
Settings that cannot be changed will respond with “Item cannot be changed” shown at the bottom of this
page.
Example 1: Some parameters will display a set of two or more xed
values.
The UPS is designed to operate with any of several discrete input volt-
ages. The value displayed in the Active Value box is the parameter
(Input Voltage) in use. Alternate values are displayed in keys below the
Active Value box.
Press the correct voltage key, then press Write to load the selected value
to the UPS memory and return to the original parameter screen.
Example 2: Some parameters can be any of a range of values.
The VIUV (Voltage In Under Voltage) Hysterisus can vary over a range.
Press the “Rated Vin” parameter listing and enter the correct value in the
Active Value box using the standard alphanumeric keypad.
Use the back arrow to delete an incorrect keystroke.
After changing the parameter value, press Write to write the entered
value to the UPS memory.
Example 3: Some parameters are informational, some can be changed
by the user, and others can only be changed by a higher security access.
If a parameter cannot be changed under the current security access
level, selecting the parameter for change will generate the message
“Item cannot be changed”.
Press OK to return to the original display.
96% 100%
On-Line
Main Monitor Settings Records
12:35 PM
INV
HOME
USR
Quit
Write
111 Rated Vin
240V
230V
5JKL
8TUV
0-:
208V
4GHI
7PQRS
240V
6MNO
9WXYZ
Shift
96% 100%
Example 1
On-Line
Main Monitor Settings Records
12:35 PM
INV
HOME
USR
Quit
Write
117 VIUV Hysteresis*
8
2 ABC
5JKL
8TUV
0-:
1./
4GHI
7PQRS
3DEF
6MNO
9WXYZ
Shift
Example 2
On-Line
DVCOH
ASYN
Main Monitor Settings Records
12:35 PM
INIT
HOME
USR
1 / 32
Item cannot be changed
OK
96% 100%
Example 3