Toshiba 1600XP Power Supply User Manual


 
D1
1600XP Series Installation and Operation Manual
Appendix D: Battery Backup Tables (Internal Batteries & Ex-
ternal Matching Battery Cabinets)
3.6kVA - UHG3G2L036C61xxx
UPS RUNTIME WITH ONLY INTERNAL BATTERIES @ .70pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
3.6 0.7 240 15.00 0.10 252 12 1 144 82
3.6 0.7 240 15.00 0.20 504 12 1 144 53
3.6 0.7 240 15.00 0.30 756 12 1 144 40
3.6 0.7 240 15.00 0.40 1008 12 1 144 29
3.6 0.7 240 15.00 0.50 1260 12 1 144 22
3.6 0.7 240 15.00 0.60 1512 12 1 144 18
3.6 0.7 240 15.00 0.70 1764 12 1 144 16
3.6 0.7 240 15.00 0.80 2016 12 1 144 12
3.6 0.7 240 15.00 0.90 2268 12 1 144 11
3.6 0.7 240 15.00 1.00 2520 12 1 144 7
UPS RUNTIME WITH INTERNAL BATTERIES AND 1 BATTERY CABINET @ .70pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
3.6 0.7 240 15.00 0.10 252 12 4 144 240
3.6 0.7 240 15.00 0.20 504 12 4 144 165
3.6 0.7 240 15.00 0.30 756 12 4 144 135
3.6 0.7 240 15.00 0.40 1008 12 4 144 105
3.6 0.7 240 15.00 0.50 1260 12 4 144 90
3.6 0.7 240 15.00 0.60 1512 12 4 144 82
3.6 0.7 240 15.00 0.70 1764 12 4 144 72
3.6 0.7 240 15.00 0.80 2016 12 4 144 65
3.6 0.7 240 15.00 0.90 2268 12 4 144 57
3.6 0.7 240 15.00 1.00 2520 12 4 144 53
UPS RUNTIME WITH INTERNAL BATTERIES AND 2 BATTERY CABINETS @ .70pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
3.6 0.7 240 15.00 0.10 252 12 7 144 300
3.6 0.7 240 15.00 0.20 504 12 7 144 300
3.6 0.7 240 15.00 0.30 756 12 7 144 180
3.6 0.7 240 15.00 0.40 1008 12 7 144 165
3.6 0.7 240 15.00 0.50 1260 12 7 144 150
3.6 0.7 240 15.00 0.60 1512 12 7 144 120
3.6 0.7 240 15.00 0.70 1764 12 7 144 112
3.6 0.7 240 15.00 0.80 2016 12 7 144 105
3.6 0.7 240 15.00 0.90 2268 12 7 144 98
3.6 0.7 240 15.00 1.00 2520 12 7 144 86