Toshiba 1600XP Power Supply User Manual


 
D10
1600XP Series Installation and Operation Manual
UPS RUNTIME WITH ONLY INTERNAL BATTERIES @ .85pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
14 0.85 240 58.33 0.10 1190 24 2 288 112
14 0.85 240 58.33 0.20 2380 24 2 288 60
14 0.85 240 58.33 0.30 3570 24 2 288 43
14 0.85 240 58.33 0.40 4760 24 2 288 29
14 0.85 240 58.33 0.50 5950 24 2 288 21
14 0.85 240 58.33 0.60 7140 24 2 288 16
14 0.85 240 58.33 0.70 8330 24 2 288 13
14 0.85 240 58.33 0.80 9520 24 2 288 11
14 0.85 240 58.33 0.90 10710 24 2 288 10
14 0.85 240 58.33 1.00 11900 24 2 288 7
UPS RUNTIME WITH INTERNAL BATTERIES AND 1 BATTERY CABINET @ .85pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
14 0.85 240 58.33 0.10 1190 24 5 288 300
14 0.85 240 58.33 0.20 2380 24 5 288 150
14 0.85 240 58.33 0.30 3570 24 5 288 98
14 0.85 240 58.33 0.40 4760 24 5 288 78
14 0.85 240 58.33 0.50 5950 24 5 288 63
14 0.85 240 58.33 0.60 7140 24 5 288 53
14 0.85 240 58.33 0.70 8330 24 5 288 45
14 0.85 240 58.33 0.80 9520 24 5 288 40
14 0.85 240 58.33 0.90 10710 24 5 288 35
14 0.85 240 58.33 1.00 11900 24 5 288 30
UPS RUNTIME WITH INTERNAL BATTERIES AND 2 BATTERY CABINETS @ .85pf
Rating PF Output
Voltage
Rated I Rated
Load %
Output
Watts
# Batt # Strings Nominal Runtime
14 0.85 240 58.33 0.10 1190 24 8 288 300
14 0.85 240 58.33 0.20 2380 24 8 288 240
14 0.85 240 58.33 0.30 3570 24 8 288 150
14 0.85 240 58.33 0.40 4760 24 8 288 120
14 0.85 240 58.33 0.50 5950 24 8 288 98
14 0.85 240 58.33 0.60 7140 24 8 288 82
14 0.85 240 58.33 0.70 8330 24 8 288 72
14 0.85 240 58.33 0.80 9520 24 8 288 63
14 0.85 240 58.33 0.90 10710 24 8 288 55
14 0.85 240 58.33 1.00 11900 24 8 288 51