B-22
1600XP Series Installation and Operation Manual
613 UPS Warnings Warnings R R R R/W R/W Only accept zero to clear Warning bit map
614 UPS System Status UPS
Status(Comm)
R R R R R LSW is attached at every data package. See the details
of bit map UX3FN19 (Toshiba Communication Protocol
(TUCP 2.0) for external Reference.doc
615 Run / Stop mechanical switch
state
RunStop SW
Status
R R R R R 0: Stop
1: Run
617 Service Port Communication
Status
SPort Status R R R R R 0 0: Unknown
1: Normal & OK
2: Idle – Off (Disable)
3: Error
618 Internal Communication StatusInter Comm Status R R R R R 0 0: Unknown
1: Normal & OK
2: Idle or Off (Disable)
3: Error
619 Security Level Control
(Enter Password)
Change Secu. Lvl R/W R/W R/W R/W R/W Reading will give the current security level
USER for User Level
ADMIN for Administration Level
DIST for Distrubutor Level
QCNSRV for Qc and Service Level
ENG for Engineering Level
NOTE: Three communication chanels have their own
security level variables
620 Manage Admin Password Manage Admin
PW
- R/W R/W R/W R/W ADMIN Change Admin Password
621 Reset Admin Password Reset Admin PW R/W R/W R/W R/W R/W 0 0 = do nothing
1 = reset administration password
623 Bypass Enable* En Bypass* - - - R/W R/W 1: Enabled DIP Switch, EEPROM’s Enable CVCF, and this value
will decide the system’s bypass availability (Restart
Required)
0: Disable
1: Enable
Item Brief Description