Operation
Smart Distribution Panel with ATS 25
How to return to powering the load from mains
1. Ensure that the ATS Automatic
Operation switch is in the Disable
position.
2. Ensure that the Source 1 switch on the
ATS is OFF (
).
3. Turn the Source 2 switch on the ATS to OFF (
):
a. Set the selector switch on the Source 2
switch to Manual.
The operating lever will swing out
when the selector switch is in Manual.
b. Turn the Source 2 switch
counterclockwise to OFF (
). You
can use the operating lever key
(provided), for easier operation.
4. Turn the Source 1 switch on the ATS to ON (
):
a. Set the selector switch on the Source 1
switch to Manual.
The operating lever will swing out
when the selector switch is in Manual.
b. Turn the Source 1 switch clockwise to
ON (
). You can use the operating
lever key (provided), for easier
operation.
c. Close the operating levers on both the Source 1 and Source 2 switches, and set the selector
switches back to Auto to lock the switches in place.