Smart Distribution Panel with ATS 27
Total Power Off
To reduce risk of electric shock or injury to persons, disconnect all sources of supply before servicing
by following this procedure:
1. Set the ATS Automatic Operation switch to Disable.
2. Set the Source 1 switch on the ATS to OFF (
):
a. Set the selector switch on the Source 1 switch to Manual.
The operating lever will swing out when the selector switch is in Manual.
b. Turn the Source 1 switch counterclockwise to OFF (
). You can use the operating lever key
(provided), for easier operation.