American Power Conversion 400V Power Supply User Manual


 
Smart Distribution Panel with ATS 37
Generator
Generator Status
Generator Status
Fuel & Runtime
Statistics & Maint.
Generator Settings
The following items are available on this menu:
Generator Status One of the following conditions is displayed to describe the Gen State:
Off: The generator is not running.
Cranking: The generator is starting.
Running: The generator is running.
Idle: The generator is running, but not powering the load.
E-Stop: The Emergency Power Off switch has been actuated on the generator or
ATS.
Fault: The generator is unable to start.
No Com: The ATS has lost communication with the generator.
The Mode Sw is the position of the generator’s
/Manual/Auto switch. The switch
must be in Auto for the generator to be started based on the state of the run/stop
contact. Auto, Manual, or Off is displayed to describe the position of the switch.
The following settings can be accessed through this menu:
Engine Run: This is the current state of the run/stop contact, which signals the
generator's engine to start and stop. The state can be Run or Off. Automatic control
of this signal is disabled when the Not in Automatic Operation LED on the ATS is
lit.
Engine Parameters: View the following measured data related to the generator's
engine operation:
–Battery Voltage
–Oil Pressure
–Coolant Temperature
–Engine RPM
–Coolant Level
–Oil Level
Fuel & Runtime The following are displayed on this screen:
• Type: The type of fuel that the generator uses (diesel).
Tank Size: The size of the fuel tank on the generator (in gallons).
Fuel Level: The percentage of fuel left in the generator fuel tank.
Runtime Estimate: How much time (xx days zz hours) the generator can run based
on the fuel level and load, and the load value, in kW, used to calculate runtime.
Statistics & Maint. Lifetime Statistics: Scroll through a list of items that accumulate over the life of
the generator, including:
–Last Maintenance Date
–Engine Starts
–Total kWh
–Total Runhours