Smart Distribution Panel with ATS 73
How to Update ATS Firmware
The InfraStruXure Smart Distribution Panel with ATS requires multiple files to be downloaded to
update the firmware. Be sure to select all relevant files from the APC website for download, and
repeat this procedure for each of the firmware files.
This section describes the instructions for upgrading the ATS control processor firmware through the
display interface, and how to download ATS firmware updates from a local computer.
Upgrading the ATS control processor
You can download available ATS control processor updates through the ATS display interface. The
most obvious indication that a firmware update is necessary occurs when the Network Management
Card and the control processor stop communicating. This lack of communication causes the ATS’s
data to no longer be accessible through the display interface and a SysData Mismatch alarm to
occur. When this alarm occurs, peform the following steps to update the ATS control processor
firmware:
1. Upgrade the ATS Network Management Card.
2. At the ATS display interface, select Config, and then Firmware Updates. You will receive the
following screen:
Press any key to download the update.
See also
To download a firmware upgrade and transfer it to your ATS, see “File Transfers” in the
InfraStruXure Power Generation System’s online Network Management Interface
User’s Guide on the Utility CD.
See also
For instructions on how to upgrade the ATS’s Network Management Card,
refer to the online Network Management Interface User’s Guide on the
Utility CD.
Note
If you do not recieve the SysData Mismatch alarm, but want to check
for available ATS control processor firmware updates, you can do so
by performing step 2 in the procedure above.
Upgrade from X.XX
To X.XX
Press a key.